7 - 9
7 User Calibration
E5@C-T Digital Temperature Controllers User’s Manual (H185)
7-5 Calibrating Analog Input
7
7-5 Calibrating Analog Input
z Calibrating a Current Input
In this example, calibration is shown for a Controller with an analog input, with a current input set as
the input type.
1. Connect the power supply.
2. Connect an STV and DMM to the current input terminals, as shown in the
following diagram.
3. Turn the power ON.
4. Move to the Calibration Level.
This starts the 30-minute aging timer. This timer provides an approximate timer for
aging. After 30 minutes have elapsed, the No. 2 display changes to 0. You can
advance to the next step in this procedure even if 0 is not displayed.
5. When the M Key is pressed, the status changes as shown to the left.
The No. 2 display at this time shows the currently entered count value in
hexadecimal. Set the STV to 20 mA.
Allow the count value on the No. 2 display to fully stabilize, then press the D Key
to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.
6. When the M Key is pressed, the status changes as shown to the left.
Set the STV to 1 mA.
Allow the count value on the No. 2 display to fully stabilize, then press the D Key
to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.
7. When the M Key is pressed, the status changes as shown to the left.
The data to be temporarily registered is not displayed if it is not complete.
Press the U Key. The No. 2 display changes to yes. Release the key and wait
two seconds or press the M Key. This stores the temporarily registered calibration
data to non-volatile memory.
To cancel the saving of temporarily registered calibration data to non-volatile
memory, press the M Key (while no is displayed in the No. 2 display) without
pressing the U Key.
8. The calibration mode is ended by turning the power OFF.
For Controllers that have a transfer output, you can continue by calibrating the
transfer output. For detailed setting methods, refer to 7-6 Calibrating the Transfer
Output.
+
−
Input power supply
STV
DMM
E5CC-T
Input power supply
STV
DMM
E5EC-T/AC-T
11
12
4
5
1
2
22
23
−
+
adj
30
a 20
c8e7
a 1
4677
str
no

Table of Contents

Other manuals for Omron E5CC-RX2ABM-000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC-RX2ABM-000 and is the answer not in the manual?

Omron E5CC-RX2ABM-000 Specifications

General IconGeneral
BrandOmron
ModelE5CC-RX2ABM-000
CategoryTemperature Controller
LanguageEnglish

Related product manuals