G3PA-(VD)
G3PA-(VD)
145
Close
Mounting
At a rated ambient temperature for each.
Note: Keep a distance of 3 cm or more between the G3PA
(especially
the SSR on the upper side) and the duct.
Screw or DIN track mounting is possible.
Mount horizontally to ground.
Panel
Close mounting of up to three G3P
A
SSRs is possible.
Load current should be reduced by 10%
for G3P
A-210B-VD, -220B-VD, -240B-
VD, and by 20% for other models.
T
o close mount more than three G3P
A,
keep a distance of 10 mm between each
SSR.
DIN
track
Panel
For
vertical mounting, the load current must
be 30% lower than the rated one (refer to
Engineering Data
).
DIN
track
G3PA
G3PA
Keep
a distance of 80 mm between
the upper SSR and the lower SSR.
Ground
Ground
Horizontal Mounting
V
ertical Mounting