3-75
3 Error Tables
NJ-series Troubleshooting Manual (W503)
3-1 Errors by Source
3
3-1-4 Errors in the EtherNet/IP Function Module
34240000 hex FTP Server
Setting Error
An error was
detected in the FTP
server settings.
Setting error
Power was interrupted when a
download was in progress for
the FTP server settings.
Memory error
S NJ-series
CPU Unit
Built-in Ether-
Net/IP Port
User’s Manual
(Cat. No.
W506)
34250000 hex NTP Client
Setting Error
An error was
detected in the NTP
client settings.
Setting error
Power was interrupted when a
download was in progress for
the NTP client settings.
Memory error
S Same as
above.
34260000 hex SNMP Set-
ting Error
An error was
detected in the
SNMP agent/trap
settings.
Setting error
Power was interrupted when a
download was in progress for
the SNMP agent/trap settings.
Memory error
S Same as
above.
34270000 hex Tag Name
Resolution
Error
Resolution of a tag
used in a tag data
link failed.
The size of the network-pub-
lished variable is different from
the tag settings.
The I/O direction set for a tag
data link and the I/O direction of
the Controller variable do not
match.
There are no network-published
variables for the Controller tag
settings.
A variable in the Controller that
is set for a tag data link has the
Network Publish attribute set to
Input but also has the Constant
attribute.
S Same as
above.
50010000 hex
(Ver. 1.02)
Controller
Insufficient
Memory
Warning
The amount of data
for the EtherCAT
slave configuration,
network-published
information, or
other data exceeds
the value that is
specified for the
CPU Unit. You may
not be able to per-
form online editing
or other operations.
The amount of data for the
EtherCAT slave configuration,
network-published information,
or other data exceeds the value
that is specified for the CPU
Unit.
S Same as
above.
84030000 hex DNS Server
Connection
Error
Connection with the
DNS server failed.
Parameter error
Server is down.
An error occurred in the com-
m
unications path.
S Same as
above.
84040000 hex NTP Server
Connection
Error
Connection with the
NTP server failed.
Parameter error
Server is down.
An error occurred in the com-
munications path.
S Same as
above.
84070000 hex Tag Data Link
Connection
Failed
Establishing a tag
data link connection
failed.
The tag data link connection
information is not the same for
the originator and target.
Insufficient connections
S Same as
above.
Event code Event name Meaning Assumed cause