3-83
3 Error Tables
NJ-series Troubleshooting Manual (W503)
3-1 Errors by Source
3
3-1-6 Errors in the DB Connection Service Function
14D30000 hex
(Ver. 1.05)
SQL Execu-
tion Failure
Log Save
Failed
Failed to save the
SQL Execution Fail-
ure Log to the SD
Memory Card.
An SD Memory Card is not
inserted.
The SD Memory Card is not the
correct type of card.
The format of the SD Memory
Card is not correct.
The SD Memory Card is write-
protected.
The capacity of the SD Memory
Card is insufficient.
The SD Memory Card is dam-
aged.
SU NJ-series
Database
Connection
CPU Units
User’s Manual
(Cat. No.
W527)
35300000 hex
(Ver. 1.05)
DB Connec-
tion Setting
Error
The DB Connec-
tion settings are not
correct.
The power supply to the Con-
troller was interrupted during a
download of the DB Connection
settings.
The DB Connection settings
are not correct because the
power supply to the Controller
was interrupted during a Clear
All Memory operation.
The DB Connection settings
are not correct because the
power supply to the Controller
was interrupted during a
Restore operation.
Non-volatile memory failed.
S Same as
above.
85100000 hex
(Ver. 1.05)
DB Connec-
tion Discon-
nected Error
The DB Connec-
tion was discon-
nected due to an
error.
The power supply to the server
is OFF.
The DB is stopped in the
server.
The Ethernet cable connector is
disconnected.
The Ethernet cable is broken.
Noise
S Same as
above.
95300000 hex
(Ver. 1.05)
DB Connec-
tion Service
Started
The DB Connec-
tion Service was
started.
The DB Connection Service
was successfully started.
S Same as
above.
95310000 hex
(Ver. 1.05)
DB Connec-
tion Service
Stopped
Th
e DB Connec-
tion Service w
as
stopped.
The DB Connection Service
was stopped.
S Same as
above.
95320000 hex
(Ver. 1.05)
DB Connec-
tion Service
Shutdown
The DB Connec-
tion Service was
shut down.
The DB Connection Service
was shut down for turning OFF
the power supply safely.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info

Table of Contents

Other manuals for Omron NJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NJ Series and is the answer not in the manual?

Omron NJ Series Specifications

General IconGeneral
Program CapacityUp to 128 MB
SD Card SlotYes
Power Supply Voltage24 VDC
Motion ControlYes
USB Ports1
Operating Temperature0°C to 55°C
Communication InterfacesEthernet/IP, EtherCAT, USB
Safety FunctionOptional
Storage Temperature-20°C to 75°C
Communication PortsUSB
DimensionsVaries by model
WeightVaries by model