Page #148 background imageLoading...
Page #148 background image
3 Error Tables
3-86
NJ-series Troubleshooting Manual (W503)
5401300B hex
(Ver. 1.05)
SQL Execu-
tion Error
The executed SQL
statement resulted
in an error.
There is no column with the
same name as a structure
member of the DB Map Vari-
able.
The table specified in the
DB_CreateMapping instruction
does not exist in the DB.
One or more structure member
values of the DB Map Variable
cannot be converted to the cor-
responding column’s data type.
One or more structure member
values of the DB Map Variable
exceed the valid range of the
corresponding column’s data
type.
The column specified in the
extraction condition does not
exist in the DB’s records.
(DB_Select instruction,
DB_Update instruction,
DB_Delete instruction)
The extraction condition has a
syntax error.
(DB_Select instruction,
DB_Update instruction,
DB_Delete instruction)
The column specified in the sort
condition does not exist in the
DB’s records.
(DB_Select instruction)
The sort condition has a syntax
error. (DB_Select instruction)
The user does not have the
access rights to the table.
S NJ-series
Database
Connection
CPU Units
User’s Manual
(Cat. No.
W527)
5401300C hex
(Ver. 1.05)
Spool Capac-
ity Exceeded
The SQL state-
ment could not be
stored in the Spool
memory because
its maximum capac-
ity was exceeded.
The DB connection failure has
been continuing due to network
failure or other factors.
The resend processing of the
SQL statements stored in the
Spool memory has not been
executed (when the Resend
spool data parameter is set to
Manual).
S Same as
above.
5401300E hex
(Ver. 1.05)
Invalid
Extraction
Condition
The entered extrac-
tion condition is
invalid.
A text string that consists of a
NULL (16#00) character only
was specified in the Where
input variable.
S Same as
above.
54013010 hex
(Ver. 1.05)
Log Code
Out of Range
The value of the
entered log code is
outside the valid
ra
nge.
A v
alue outside the valid range
from 0 to 9999 was specified.
S Same as
above.
54013011 hex
(Ver. 1.05)
DB Connec-
tion Discon-
nected Error
Status
The instruction
could not be exe-
cuted because the
DB Connection had
been disconnected
due to an error.
The power supply to the server
is OFF.
The DB is stopped in the
server.
The Ethernet cable connector is
disconnected.
The Ethernet cable is broken.
Noise
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info

Table of Contents

Other manuals for Omron NJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NJ Series and is the answer not in the manual?

Omron NJ Series Specifications

General IconGeneral
Program CapacityUp to 128 MB
SD Card SlotYes
Power Supply Voltage24 VDC
Motion ControlYes
USB Ports1
Operating Temperature0°C to 55°C
Communication InterfacesEthernet/IP, EtherCAT, USB
Safety FunctionOptional
Storage Temperature-20°C to 75°C
Communication PortsUSB
DimensionsVaries by model
WeightVaries by model

Related product manuals