3 Error Tables
3-140
NJ-series Troubleshooting Manual (W503)
The section provides tables of the events that can occur in the following Units.
CJ1W-DRM21
CJ-series DeviceNet Units
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info
04880000 hex Unit Memory
Error
An error occurred
when writing to
internal memory
where the error his-
tory is saved.
• There is a source of noise
nearby.
• Non-volatile memory failure
SU CJ-series
DeviceNet
Units Opera-
tion Manual for
NJ-series
CPU Unit (Cat.
No. W497)
04890000 hex Network
Power Error
Network power is
not being supplied.
• Communications power is not
being supplied normally from
the network.
S Same as
above.
148D0000 hex Invalid Scan
List Data
There is an error in
the contents of the
slave scan list or
master scan list
stored in non-vola-
tile memory.
• The power was interrupted dur-
ing writing the scan list to the
non-volatile memory.
S Same as
above.
148E0000 hex Invalid Setup
Data
There is illegal data
in the settings for
the slave function.
• The power was interrupted
while the system was writing
the parameters.
• Non-volatile memory life
S Same as
above.
24480000 hex Node
Address
Duplicated
Error
An error was dis-
covered during the
node address dupli-
cation check when
starting the
DeviceNet Unit.
• The node address of the
DeviceNet Unit is also set for
another node.
S Same as
above.
34BC0000 hex Routing Table
Error
There is illegal data
in the routing tables
set in the CPU Unit.
• The local DeviceNet Unit is not
in the routing tables.
• The routing table format is
incorrect.
• Reading the routing tables
timed out.
SU Same as
above.