2 Error Troubleshooting Methods
2-16
NJ-series Troubleshooting Manual (W503)
Remote Connection to Peripheral USB Port
End
No
No
No
No
No
No
No
No
No
No
Insert the cable connectors all the way
at the computer and Controller.
Turn ON the power supply to the Controller.
Is power supplied to the Controller?
Can the Sysmac Studio
go online with CPU Unit?
Can the Sysmac Studio
go online with CPU Unit?
Sysmac Studio cannot
connect to CPU Unit.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Is the connection method set
to a remote USB connection
in the Communications Setup
of the Sysmac Studio?
Set the connection method to a remote USB
connection in the Communications Setup of
the Sysmac Studio. Set the destination IP
address for a remote USB connection or
Ethernet-hub connection in the Communica-
tions Setup of the Sysmac Studio.
Can the Sysmac Studio
go online with CPU Unit?
Can the Sysmac Studio
go online with CPU Unit?
Can the Sysmac Studio
go online with CPU Unit?
Is the destination
IP address for a remote USB
connection or Ethernet-hub connection
in the Communications Setup of the
Sysmac Studio set correctly and is the
IP address set correctly in the
destination Controller?
Correct the destination IP address for a
remote USB connection or Ethernet-hub
connection in the Communications Setup of
the Sysmac Studio. Correct the IP address
setting in the destination Controller.
Is the USB driver installed
correctly?
Install the USB driver. Refer to the
appendices of Sysmac Studio Version 1
Operation Manual (Cat. No. W504) for the
installation procedu
re for the USB driver.
Replace the USB cable
, or the Ethernet cables
and Ether
net switches between the computer
and the Controller.
Are the USB cable and
Ethernet cables
connected properly?