5 Troubleshooting
5-14
NJ-series CPU Unit Hardware User’s Manual (W500)
10080000 hex Main Memory
Check Error
An error was
detected in the
memory check of
the main memory in
the CPU Unit.
Conductive material has gotten
inside.
•Noise
There is a software error.
The CPU Unit has failed.
S page 5-34
100A0000 hex
(Ver. 1.10 or
later)
Data Not
Saved to Bat-
tery-backup
Memory
An error occurred in
the software and
data could not be
saved in battery-
backup memory
during power-OFF
processing.
An error occurred in the soft-
ware.
S page 5-35
100B0000 hex Non-volatile
Memory Data
Corrupted
A file that must be
in non-volatile
memory is missing
or corrupted.
The Controller power supply
was turned OFF while the
BUSY indicator was lit.
The power supply to the Con-
troller was interrupted momen-
tarily while the BUSY indicator
was lit.
The CPU Unit has failed.
S page 5-36
100C0000 hex
(Ver. 1.03 or
later)
Event Level
Setting Error
The settings in the
event level setting
file are not correct.
The event level settings are not
correct because the power sup-
ply to the Controller was inter-
rupted or communications with
the Sysmac Studio were dis-
connected during a download
of the event level settings.
The event level settings are not
correct because the power sup-
ply to the Controller was inter-
rupted during a Clear All
Memory operation.
Non-volatile memory failed.
S page 5-37
40010000 hex PLC System
Processing
Error
A fatal error was
detected in the PLC
Function Module.
An error occurred in the soft-
ware.
S page 5-37
40020000 hex PLC System
Processing
Error
A fatal error was
detected in the PLC
Function Module.
An error occurred in the soft-
ware.
S page 5-38
40030000 hex PLC System
Processing
Error
A fatal error was
detected in the PLC
Function Module.
An error occurred in the soft-
ware.
S page 5-38
00070000 hex Real-Time
Clock
Stopped
The oscillation of
the real-time clock
stopped. The real-
time clock is set to
an illegal time.
The battery voltage is low.
The battery connector has
come loose.
The Battery is missing.
S U page 5-39
00080000 hex Real-Time
Clock Failed
The real-time clock
in the CPU Unit
failed.
The CPU Unit clock has failed. S page 5-39
00
0
B0000 hex Low Battery
Voltage
The voltage of the
Battery has
dropped.
The battery voltage is low.
The battery connector has
come loose.
The Battery is missing.
S U page 5-40
000C0000 hex CPU Unit
Overheat
The temperature
inside the CPU Unit
exceeded the spec-
ified value.
The ambient operating tem-
perature is too high.
S page 5-40
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info