What to do if a specific output does not turn OFF, but the operation indicator is not lit on Omron NJ501-1400?
- NnharrisSep 12, 2025
If a specific output on your Omron Control Unit does not turn OFF, but the operation indicator is not lit, it could be due to: * The output relay being faulty for a Relay Output Unit. Replace the Output Unit. * The leakage current or residual voltage preventing resetting. Replace the external load or add a dummy resistor.