Machine Automation Controller
NJ-series
CPU Unit
Hardware
CPU Unit
Power Supply Unit
Basic I/O Units
User’s Manual
W500-E1-17
NJ501-
NJ301-1
NJ101-
NJ-P3001
CJ1W-ID/IA
CJ1W-INT01
CJ1W-IDP01
CJ1W-OC/OD/OA
CJ1W-MD
CJ1W-B7A

Table of Contents

Questions and Answers

  • R
    Rebecca MurphyAug 20, 2025
    How to fix Omron NJ501-1400 when none of the inputs turn ON and the operation indicators do not light?
    • A
      abbottryanAug 20, 2025
      If none of the inputs on your Omron Control Unit are turning ON and the operation indicators are not lit, check the following: * Ensure that the external input power is supplied. * Verify that the external input power supply voltage is within the specified rating. * Tighten any loose screws on the terminal block. * If there is still no improvement, replace the terminal block or connector if there is faulty contact.
  • A
    Anna MurphyAug 22, 2025
    What to do if none of the outputs turn ON on my Omron Control Unit?
    • W
      Wendy HobbsAug 22, 2025
      If none of the outputs on your Omron Control Unit are turning ON, check these potential causes: 1. Ensure that the load power is supplied. 2. Maintain the power supply voltage within the rating. 3. Tighten any loose screws on the terminal block. 4. Replace the terminal block or connector if there is faulty contact. 5. Replace the Unit if the fuse in the Output Unit has burned out due to overcurrent. 6. Replace the Output Unit if there is faulty contact on Unit connector or faulty output circuits. 7. Check the load and output wiring if load short-circuit protection has operated.
  • J
    Jonathan MeyerAug 25, 2025
    Why do the input bits turn ON and OFF irregularly on my Omron Control Unit?
    • L
      Leslie FreemanAug 25, 2025
      If the input bits on your Omron Control Unit are turning ON and OFF irregularly, consider the following: * Maintain the external input power supply voltage within the rating, as a low or unstable voltage can cause this issue. * Implement noise countermeasures to address potential malfunction caused by noise. * Ensure the terminal block screws are tightened. * Replace the terminal block or connectors if there's faulty contact.
  • T
    terripruittAug 26, 2025
    What to do if a specific input does not turn ON on Omron NJ501-1400 Control Unit?
    • T
      tara90Aug 26, 2025
      If a specific input on your Omron Control Unit does not turn ON, check these potential issues: 1. Replace the input device if it is faulty. 2. Check the input wiring for any breaks. 3. Ensure that the screws on the terminal block are tightened. 4. Replace the terminal block or connector if there is faulty contact. 5. Adjust the input device or correct the setting of the input response time if the external input ON time is too short or the input response time is too long. 6. Replace the Input Unit if there are faulty input circuits. 7. Correct the user program if an input bit is used in an Out instruction.
  • T
    Tammy CookAug 27, 2025
    Why does the output turn ON and OFF irregularly on my Omron NJ501-1400?
    • R
      roseryanAug 28, 2025
      If the output on your Omron Control Unit turns ON and OFF irregularly, consider the following: 1. Maintain the load power supply voltage within the rating, as a low or unstable voltage can cause this issue. 2. Correct the user program so that only one Out instruction controls the output bit if the output bit is used in more than one Out instruction. 3. Implement noise countermeasures to address potential malfunction caused by noise. 4. Ensure the terminal block screws are tightened. 5. Replace the terminal block or connectors if there's faulty contact.
  • D
    Danny HurleyAug 29, 2025
    What causes abnormal operation for the output points for the same common on Omron NJ501-1400?
    • C
      Christine MartinAug 30, 2025
      If there is abnormal operation for the output points for the same common (8 or 16 points) on your Omron Control Unit, check the following: * Ensure that the screws on the common terminal are tightened. * Replace the terminal block or connector if there is faulty contact. * Replace the Output Unit if the fuse in the Output Unit has burned out due to overcurrent, or if there are faulty circuits in the Output Unit. * Replace the CPU Unit if it is faulty. * Check the load and output wiring if load short-circuit protection has operated.
  • J
    James WhiteAug 31, 2025
    What to do if a specific output does not turn ON, but the operation indicator is lit on Omron Control Unit?
    • L
      Laura SmithAug 31, 2025
      If a specific output on your Omron Control Unit does not turn ON, but the operation indicator is lit, it could be due to: * A faulty output device (replace the device). * Broken output wiring (check the output wiring). * Loose screws on the terminal block (tighten the screw). * Faulty contact on the terminal block or connectors (replace the terminal block or connector). * A faulty relay for a Relay Output Unit (replace the Output Unit). * Faulty output circuits (replace the Output Unit).
  • J
    Jennifer StewartSep 2, 2025
    What to do if none of the inputs turn ON, but the operation indicators are lit on Omron NJ501-1400?
    • M
      Mary GonzalezSep 2, 2025
      If none of the inputs turn ON, but the operation indicators are lit on your Omron Control Unit, the issue could be faulty circuits in the Input Unit. In this case, replace the Input Unit.
  • P
    Pamela ClarkSep 4, 2025
    What causes abnormal operation for the input points for the same common on Omron NJ501-1400 Control Unit?
    • D
      Deborah MahoneySep 4, 2025
      If abnormal operation occurs for the input points for the same common (8 or 16 points) on your Omron Control Unit, check for the following: 1. Tighten any loose screws on the common terminal. 2. Replace the terminal block or connector if there is faulty contact. 3. Replace the Input Unit if there are faulty circuits in the Input Unit. 4. Replace the CPU Unit if it is faulty.
  • S
    Stephanie ThomasSep 6, 2025
    What to do if a specific output does not turn OFF and the operation indicator is lit on Omron NJ501-1400 Control Unit?
    • N
      Nicholas RandallSep 6, 2025
      If a specific output on your Omron Control Unit does not turn OFF and the operation indicator is lit, the issue may be due to: * The output bit being used in more than one Out instruction in the user program. Correct the user program so that only one Out instruction controls the output bit. * Faulty output circuits. Replace the Output Unit.

Omron NJ501-1400 Specifications

General IconGeneral
ModelNJ501-1400
Built-in Ethernet portYes
Built-in USB portYes
Power supply voltage24 VDC
Power consumption30 W
Operating temperature0 to 55 °C
Protection ratingIP20
Cycle Time1 ms
Built-in EtherNet/IP portYes
Built-in EtherCAT portYes
Programming languageIEC 61131-3 (LD, ST, FBD, SFC, IL)
Storage temperature-25 to 70 °C
Operating humidity10 to 90% RH (non-condensing)
Vibration resistance10 to 57 Hz, 0.075 mm amplitude, 57 to 150 Hz, 9.8 m/s² acceleration
Shock resistance150 m/s²

Related product manuals