Appendix DData Memory Coding Sheet
125
DM word
Setting contents
Use Designation
15 8 7 0
Use designationm
m+1
m+2
m+3
m+4
m+5
m+6
m+7
m+8
m+9
Output signal range setting
Output 1: Output
status when con-
version stopped
Output 2: Output
status when con-
version stopped
Output 3: Output
status when con-
version stopped
Output 4: Output
status when con-
version stopped
Output 5: Output
status when con-
version stopped
Output 6: Output
status when con-
version stopped
Output 7: Output
status when con-
version stopped
Output 8: Output
status when con-
version stopped
07 06 05 04 03 02 01 00
Output 8
07 06 05 04 03 02 01 00
15 14 13 12 11 10 09 08
07 04 03 00
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2
Output 1
Output 4
Output 3
Output 2
Output 1
Output 8
Output 7
Output 6
Output 5
16
3
16
2
Output Status When Conversion Stopped
0: Do not use.
1: Use.
00: -10 to 10 V
01: 0 to 10 V
10: 1 to 5 V / 4 to 20 mA
11: Same as 10 above
Signal Range Setting (Not Valid for C200H-DA004)
00: CLR (0 output)
01: HOLD (Hold prior output value.)
02: MAX (Output maximum value of range.)