OPERATION MANUAL
Cat. No. W345-E1-08
SYSMAC CS/CJ Series
CS1W-AD041-V1/AD081-V1/AD161
CS1W-DA041/DA08V/DA08C
CS1W-MAD44
CJ1W-AD041-V1/AD081-V1
CJ1W-DA021/DA041/DA08V/DA08C
CJ1W-MAD42
Analog I/O Units

Table of Contents

Questions and Answers

  • D
    Danny ArroyoAug 9, 2025
    What to do if conversion data does not change on Omron CS1W-AD081-V1 I/O Systems?
    • N
      Nathan MasonAug 9, 2025
      If the conversion data on your Omron I/O Systems isn't changing, ensure the input is set to be used. Also, check if the peak value hold function is active and turn it off if not needed. Use a tester to verify the input voltage or current is changing and check the Unit’s alarm flags for a disconnection.
  • E
    Eric SchultzAug 18, 2025
    Why value does not change as intended on Omron CS1W-AD081-V1?
    • C
      camposrobertAug 19, 2025
      If the value on your Omron I/O Systems isn't changing as intended, verify that the input device’s signal range matches the input signal range for the relevant input number at the Analog Input Unit. Make sure you adjust the offset and gain. If you're using the 4 mA to 20 mA range, ensure the voltage/current switch is turned ON.
  • L
    lewisabigailAug 29, 2025
    How to fix inconsistent conversion values in Omron CS1W-AD081-V1 I/O Systems?
    • B
      Brandy NorrisAug 29, 2025
      If you're experiencing inconsistent conversion values on your Omron I/O Systems, it might be due to external noise affecting the input signals. Try changing the shielded cable connection to the Unit’s COM terminal. Additionally, insert a 0.01-µF to 0.1-µF ceramic capacitor or film capacitor between the input’s (+) and (–) terminals. You can also try increasing the number of mean value processing buffers.

Summary

SYSMAC CS;CJ Series

Analog I;O Units

Describes the types of analog I/O units covered in the manual, including input, output, and combined units.

PRECAUTIONS

General Precautions

Fundamental safety and operational guidelines for using OMRON products.

Safety Precautions

Critical safety warnings and procedures to prevent injury or damage.

Application Considerations

SECTION 2 CS-series Analog Input Units

2-2 Operating Procedure

Step-by-step instructions for operating CS-series Analog Input Units.

2-6 Analog Input Functions and Operating Procedures

Details on analog input functions and their operational procedures.

2-8 Handling Errors and Alarms

Troubleshooting guide for errors and alarms in Analog Input Units.

SECTION 3 CJ-series Analog Input Units

3-2 Operating Procedure

Step-by-step instructions for operating CJ-series Analog Input Units.

3-6 Analog Input Functions and Operating Procedures

Details on analog input functions and their operational procedures.

3-8 Handling Errors and Alarms

Troubleshooting guide for errors and alarms in Analog Input Units.

SECTION 4 CS-series Analog Output Units

4-2 Operating Procedure

Step-by-step instructions for operating CS-series Analog Output Units.

4-6 Analog Output Functions and Operating Procedures

Details on analog output functions and their operational procedures.

4-8 Handling Errors and Alarms

Troubleshooting guide for errors and alarms in Analog Output Units.

SECTION 5 CJ-series Analog Output Unit

5-2 Operating Procedure

Step-by-step instructions for operating CJ-series Analog Output Units.

5-6 Analog Output Functions and Operating Procedures

Details on analog output functions and their operational procedures.

5-8 Handling Errors and Alarms

Troubleshooting guide for errors and alarms in Analog Output Units.

SECTION 6 CS-series Analog I;O Unit

6-2 Operating Procedure

Step-by-step instructions for operating CS-series Analog I/O Units.

6-6 Analog Input Functions and Operating Procedures

Details on analog input functions and their operational procedures.

6-7 Analog Output Functions and Operating Procedures

Details on analog output functions and their operational procedures.

6-10 Handling Errors and Alarms

Troubleshooting guide for errors and alarms in Analog I/O Units.

SECTION 7 CJ-series Analog I;O Unit

7-2 Operating Procedure

Step-by-step instructions for operating CJ-series Analog I/O Units.

7-6 Analog Input Functions and Operating Procedures

Details on analog input functions and their operational procedures.

7-7 Analog Output Functions and Operating Procedures

Details on analog output functions and their operational procedures.

7-10 Handling Errors and Alarms

Troubleshooting guide for errors and alarms in Analog I/O Units.

Appendix B Sample Programs

Appendix C Data Memory Coding Sheets

Omron CS1W-AD081-V1 Specifications

General IconGeneral
Number of Channels8
Power Supply5 V DC
Operating Temperature0 to 55 °C
TypeAnalog Input
Input Range0 to 10 V, 0 to 20 mA, 4 to 20 mA
Sampling Time/Conversion Time1ms per channel
Current Consumption100 mA
IsolationPhotocoupler isolation between input and internal circuit
Storage Temperature-25 to 65 °C
Relative Humidity35 to 85% (with no condensation)
Noise Immunity±2 kV
StandardsCE, UL