What to do if conversion data does not change on Omron CJ1W-AD081-V1 I/O Systems?
- JJoanna CharlesAug 8, 2025
If the conversion data on your Omron I/O Systems isn't changing, ensure the input is set to be used. Also, check if the peak value hold function is active and turn it off if not needed. Use a tester to verify the input voltage or current is changing and check the Unit’s alarm flags for a disconnection.