EasyManua.ls Logo

Osburn 3500 - Floor Protector; Reducing Wall and Ceiling Clearances Safely

Osburn 3500
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 32
Installation and Operation Manual - Osburn 3500
7.3 Floor Protector
If the wood fire is to be installed on top of a combustible floor, it must be guarded by a non-
combustible material as shown on the dotted line area of the above figures. Install a 910 mm
(Width) x 1185 mm (Depth) floor protection of 6 mm of thickness with thermal conductivity of
0.026 m2 K/W per 6 mm thick.
FLOOR
PROTECTION
1
D 300 mm
E 200 mm
2
D
E
Figure 13: Floor Protection
7.4 Reducing Wall and Ceiling Clearances Safely
You may decrease the minimum clearances
to heat-sensitive materials by installing heat
radiation shields between the walls or the ceiling
and the wood fire. These heat radiation shields
must be installed permanently, and must be made
of a heat-resistant or heat-tolerant material.
An air gap must separate the heat shield from
any heat-sensitive surface. Furthermore, the
heat shield shall extend in all directions beyond
the boundaries of the appliance surface by a
distance of not less than 450 mm. Exceptions
may apply. Refer to AS/NZS 2918:2001.
Figure 14: Heat shield
Following the installation of such heat radiation shields, the minimum clearances to heat-sensitive
materials may be reduced by applying the clearances factor in the table below:
1 Bellis board, cement ber sheet or similar. No protection is required if the unit is installed on a non-combustible oor (ex: concrete).
2 The oor protector shall extend not less than 200 mm from each side of any ash removal or fuel loading openings unless the oor protector forms
an abutment with a wall or heat shield at a lesser distance.

Table of Contents

Related product manuals