HERU IQ S – HERU IQ T
OPERATION & MAINTENANCE
|
EN
UPDATE
YOUR HERU
To ensure optimal function and
performance of your Heru Air Handling
Unit, please download and install
the latest software version
ostberg.com/updates
UPDATE
YOUR HERU
To ensure optimal function and
performance of your Heru Air Handling
Unit, please download and install
the latest software version
ostberg.com/updates
Other languages in digital format can be downloaded at www.ostberg.com

Other manuals for OSTBERG HERU 100 T EC

Questions and Answers

  • S
    Stephanie Miles MDSep 23, 2025
    Why does the wireless display show the wrong temperature on OSTBERG HERU 100 T EC?
    • L
      Lance ObrienSep 23, 2025
      When the unit starts, the wireless display shows the wrong temperature because the unit is not correctly installed. All electrical installations must be performed by a qualified electrician. Order reinstallation if needed.
  • M
    Michael WatkinsAug 23, 2025
    What to do if OSTBERG Air Handlers are overheating?
    • D
      Darryl ThorntonAug 25, 2025
      If your OSTBERG Air Handlers are overheating, the overheating protection in the electric after heater may have been triggered. Cut power to the unit, check if the manual overheating protection in the electric after heater has triggered, reset the manual overheating protection, and then reset the alarm.
  • M
    Mark NewtonAug 25, 2025
    How to troubleshoot motor failure in OSTBERG HERU 100 T EC Air Handlers?
    • V
      Victor MartinAug 25, 2025
      If you're experiencing motor failure in your OSTBERG Air Handlers, it could be due to no power or signal to the fans and quick connectors, or a blocked fan wheel. Check that the fan is working and correctly connected (replace if broken), and ensure the fan wheel turns freely.
  • A
    Amy HartAug 27, 2025
    Why is the rotor temperature low in OSTBERG HERU 100 T EC?
    • D
      David VazquezAug 27, 2025
      A low rotor temperature in OSTBERG Air Handlers can be caused by dirty filters, a slipping rotor belt, or a stuck rotor. Try changing the filters, replacing the rotor belt, and ensuring that the rotor can rotate freely.
  • J
    Julie FernandezAug 27, 2025
    What causes freeze protection activation in OSTBERG HERU 100 T EC?
    • L
      Lindsay CannonAug 27, 2025
      If the freeze protection is activated in your OSTBERG Air Handlers, it may be due to insufficient heat capacity in the heating coil or a valve actuator that isn't opening correctly. Ensure that the heating coil and valve actuator are working before start-up.
  • M
    Marvin CrawfordSep 15, 2025
    How to resolve freeze protection issues in OSTBERG HERU 100 T EC Air Handlers?
    • A
      Allison SavageSep 15, 2025
      If your OSTBERG Air Handlers is experiencing freeze protection issues, it could be due to insufficient heat capacity in the heating coil or the valve actuator not opening correctly. Ensure that the heating coil and the valve actuator are working before start-up.
  • C
    Cristian SampsonSep 12, 2025
    What does 'sensor shorted' mean on OSTBERG HERU 100 T EC Air Handlers?
    • M
      Melissa WilliamsSep 13, 2025
      A 'sensor shorted' message on your OSTBERG Air Handlers means that the connection to the relay card has been broken, or the sensor itself is broken. Check which sensor is activated and the connection to the relay card. If the fault remains, change the broken sensor.
  • M
    Mrs. Angela BradshawSep 14, 2025
    What to do if OSTBERG Air Handlers triggers a fire alarm?
    • B
      baileysonyaSep 14, 2025
      If your OSTBERG Air Handlers triggers a fire alarm, it could be due to the fire alarm access being activated or an alarm signal from external alarm units. Check that the correct input function has been selected and ensure that the external alarm units are working as they should before start-up.
  • L
    Louis HayesSep 5, 2025
    What causes low rotor temperature in OSTBERG HERU 100 T EC?
    • B
      brianrossSep 5, 2025
      Low rotor temperature in OSTBERG Air Handlers can be caused by dirty filters, a slipping rotor belt, or a stuck rotor. Change the filters, replace the rotor belt, and ensure that the rotor can rotate freely.
  • O
    owensmeaganSep 2, 2025
    What to do if my OSTBERG HERU 100 T EC unit does not start?
    • C
      Claudia RaySep 2, 2025
      If your OSTBERG Air Handlers unit isn't starting, the possible causes are: the unit receives no power, the activate mode is set to “Off”, or the unit is not correctly connected. Check the fuse, residual current device, and connections to ensure the unit is receiving power. Change the mode to “On.” Ensure the unit is correctly connected.

Summary

Product Overview and Use

Control Functions

Explains how to regulate air temperature and fan capacity for the HERU units.

Safety Information

Warnings and Cautions

Highlights warnings related to personal injury and equipment damage during operation and maintenance.

General Safety Guidelines

Provides essential safety guidelines for operating and maintaining the HERU unit.

Operation and Control

Temperature and Fan Control

Explains temperature regulation modes, fan capacity adjustment, and activating features like night cooling.

Maintenance Procedures

Maintenance Schedule and Tasks

Outlines the recommended inspection and maintenance schedule, including six-month and annual tasks.

Maintenance Every Six Months

Details the inspection procedures for supply and exhaust air functions performed every six months.

Maintenance Every Year

Outlines the annual maintenance tasks, including cleaning fans and changing filters.

Troubleshooting Guide

Alarm and Malfunction Resolution

Details causes and operations for various alarms and other unit malfunctions.

Troubleshooting Chart

Offers a diagnostic flowchart to help identify and resolve specific unit operational problems.

OSTBERG HERU 100 T EC Specifications

General IconGeneral
Weight5.5 kg
MotorEC motor
Supply voltage230 V
Phase1~
Frequency50 Hz
Duct connection125 mm
Power input30-270 W
MaterialGalvanized steel