RFE 200 R
Single inlet radial fan with forward curved impeller. Single phase
RFT 200 S
Single inlet radial fan with forward curved impeller. 3-phase
PRESSURE/FLOW
TECHNICAL DATA
SOUND DATA
INPUT/FLOW
RFE 200 R
RFE 200 R, 115 l/s 525 Pa L
pA
L
wA
tot dB (A) 63 125 250 500 1K 2K 4K 8K
Environment 67 74 41 47 57 66 68 69 67 62
Inlet 75 54 60 67 63 70 68 65 63
Outlet 76 56 56 64 66 74 67 67 64
DIMENSIONS (mm)
ACCESSORIES
Duct clamp, mounting bracket, safety grille, thermostat,
louvre & back draught shutter, transformer controllers
General fan facts, page 30-31.
Voltage, V/Hz 230/50
Current, A 1,10
Input, W 260
Speed, rpm 2300
Wiring diagram 4040001
Capacitor, µF 4
Max.temp.
o
C50
Rotation direction Left
Pole number, motor 2
PRESSURE/FLOW
TECHNICAL DATA
SOUND DATA
INPUT/FLOW
RFT 200 S
RFT 200 S, 90 l/s 745 Pa L
pA
L
wA
tot dB (A) 63 125 250 500 1K 2K 4K 8K
Environment 71 78 43 47 60 67 72 76 71 67
Inlet 79 62 69 72 72 70 76 68 69
Outlet 82 65 67 71 74 75 78 75 68
DIMENSIONS (mm)
ACCESSORIES
Duct clamp, mounting bracket, safety grille, thermostat,
louvre & back draught shutter, transformer controllers
Fakta om fläktar se sidorna 30-31.
275
123
180
316
Voltage, V/Hz 3x400Y/3x230/50
Current, A 0,82/1,42
Input, kW 0,53
Speed, rpm 2340
Wiring diagram 4040004/4040003
Capacitor, µF -
Max.temp.
o
C40
Rotation direction Left
Pole number, motor 2
Connected = Connected on outlet.
Not connected = Not connected on outlet.
Connected = Connected on outlet.
Not connected = Not connected on outlet.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the OSTBERG RF and is the answer not in the manual?

OSTBERG RF Specifications

General IconGeneral
BrandOSTBERG
ModelRF
CategoryFan
LanguageEnglish

Related product manuals