Product description "R-Tronic" + "R-Con"
16
3.2 Technical data
"R-Tronic RT B / RTF B / RTFC K"
Power supply: "RTFC K" with external power pack
(100-240 V / 50-60 Hz)
"RT B", "RTF B" battery operated
(AA 1.5 V, Mignon LR6), optional mains operation
Display: LC-Display
Radio frequency: 868.3MHz
Transmitting power max.: 10 mW
Radio range within building:
Depending on materials and interference sources
Transmission interval: 150 seconds
Operation mode: Type 1 (EN 60730-1)
Protection: IP20 (EN 60529)
Protective system: III - Protective low voltage
Ambient temperature: +5 °C up to +50 °C
Measuring range T (°C): +0 °C up to +50 °C
Accuracy at +25 °C: ± 1 K
Measuring range RH (%): 0 up to 100 % RH, only for "RTF B" and "RTFC K"
Accuracy at +25 °C
and 20-80% RH: ± 4,5% RH
Measuring range CO2
(PPM): 0 up to 2000 PPM, only for "RTFC K"
Accuracy at 25 °C
and 1013 mbar: < ± 50 PPM +2% of measured value
Temperature dependence: typ. 2 PPM CO2/°C (0…50 PPM)
Long-term stability: typ. 20 PPM/a
Casing: ABS (ASA), trafc white similar to RAL 9016
Casing dimensions: 85 x 85 x 35 mm (W x H x D)
Type plates
Subjecttotechnicalmodicationwithoutnotice!