11
3.1.2 Selection of Electrical Wiring
The recommended wiring size is shown in the table 3-1.
Type of Unit
Window & Commercial Type Unit
Split Type (Separate Type)
Table 3-1 SELECTION OF ELECTRICAL WIRING
Starting
current (A)
Size of electrical wiremm
2
Remark or Remark +②(heat-resistance Temperature:
60°C[140°F]: min.
Remark③(heat-
resistance
Temperature:
120°C[248°F]
min.
5m max.
10m max.
15m max.
20m max.
30m max.
50m max.
1m max.
20max.
2.0
2.0
2.0
3.5
5.5
8.0
2.0
30max.
3.5
5.5
14.0
40max.
3.5
5.5
8.0
50max.
8.0
14.0
22.0
60max.
5.5
70max.
3.5
8.0
14.0
3.5
80max.
22.0
30.0
90max.
14.0
100max.
8.0
38.0
110max.
120max.
5.5
22.0
30.0
140max.
14.0
50.0
5.5
160max.
22.0
180max.
38.0
60.0
8.0
200max.
8.0
30.0
220max.
50.0
80.0
240max.
14.0
CAUTION OF GROUNDING:
The internal motor protector cannot protect the compressor against all possible failures.
Please be sure that the system utilizes the grounding connection when is installed in the field.
Power
terminal
compresso
indoor
Power
source
terminal
plate
compressor
indoor
compressor
indoor
Power
source
terminal
plate