EasyManua.ls Logo

Panasonic CS-A24BB4P

Panasonic CS-A24BB4P
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquid
Compression
Protection,
Crankcase
Heater
Input
power
W 31-37 31-37 31-37 31-37 31-37 34-41
Compressor
OFF
°C 160 165 120* 115 135 120
Protection,
50Hz
Internal °C 165 165 - - 140 135
Protector
60Hz
ON °C
50Hz
90 102 90*
61
61 61
°C
60Hz
105 105 - - 61 61
Trip time
50Hz
5-15sec/
55A
5-15sec/
55A
- 10sec/44A 10sec/40A 10sec/40A
10sec
60Hz
3-9sec/
96A
3-9sec/
96A
- - 10sec/85A 10sec/85A
For Fan
Motor
Protection,
OFF °C 135 135 135 135 135 135
Internal
Protector
(49F)
ON °C 85 85 85 85 85 85
Heating
Pressure
Switch (Heat
OFF
MPa
2.35 2.35 2.35 2.35 2.35 2.35
Pump Only)
(Fan Speed)
(63H
2
)
ON
MPa
2.25 2.25 2.25 2.25 2.25 2.25
Cooling
Control,
Control
Th 30 degree celcius ----- High speed
Heat
Exchanger
method
Th < 30 degree celcius ------5 speed step control
Outlet Temp.
Thermistor
(Th2)
For Control
Protection,
Fuse
CUT A 6.3 6.3 6.3 6.3 6.3 6.3
1MPa = 10.2 kgf/cm
2 /
* Head Thermostat only for CU-A28BBP8 / CU-C28BBP8