(No refrigerant in the refrigeration cycle)
1. Connect the vacuum pump to the manifold gauge’s
centre hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -0.01
MPa.
3. Close the valve (Low side) on the manifold gauge, turn
off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after
turning off the vacuum pump).
4. Disconnect the manifold gauge from the vacuum pump.
Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.
11.1.5. Evacuation
Procedure:
49
CS-C18DKV CU-C18DKV / CS-C24DKV CU-C24DKV