12.3. Automatic Operation
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting
temperature as shown in below table.
• The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as
shown in below table by pressing on the temperature up or temperature down button at remote control.
• The operation mode judging temperature and standard setting temperature can be increased by 2qC permanently, by open the
circuit of JX03 at indoor electronic controller.
12.4. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
12.4.1. Fan Speed Rotation Chart
COOL/DRY CS-C18HKD CS-C24HKD
S Hi 1460 1590
Hi 1400 1500
Me 1250 1390
H Lo 1220 1330
C Lo 1150 1240
Lo- 980 1100
S Lo 780 860
Q Hi 1300 1400
Q Me 1150 1290
Q Lo 1050 1140