12.5.3 Horizontal Airflow
12.5.3.1 E12JKK-1
The horizontal airflow direction louvers can be adjusted manually by hand.
12.5.3.2 E18JKK-1
• Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the
angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below.
• Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated below and
the positions of the vane are as figure below:
12.6 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)
• Purpose
o To provide quiet cooling operation compare to normal operation.
• Control condition
o Quiet operation start condition
When “Quiet” button at remote control is pressed.
Quiet LED illuminates.
o Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
• Powerful button is pressed.
• Stop by OFF/ON button.
• OFF Timer activates.
• Quiet button is pressed again.