9.3.1.3. Cooling Operation
9.3.1.3.1. Thermostat control
•
• •
•
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
•
• •
•
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
9.3.1.4. Soft Dry Operation
9.3.1.4.1. Thermostat control
•
• •
•
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C.
•
• •
•
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
9.3.1.5. Heating Operation
9.3.1.5.1. Thermostat control
•
• •
•
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < +2.0°C.
•
• •
•
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
63
CS-ME7DKEG CS-ME10DD3 EG / CS-ME10DTEG CS-E15DB4EW