98 
14.1.4 Compressor Overheating Prevention Control 
  Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The 
changes of frequency are as below. 
  If compressor discharge temperature exceeds 107°C, compressor will be stopped, occurs 4 times per 20 minutes, 
timer LED will be blinking. (“F97” is indicated.) 
 
 
 
14.1.5  Low Pressure Prevention Control (Gas Leakage Detection) 
  Control start conditions 
o  For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A 
(E7/9/12/15NK), 1.38A and 1.65A (E18NK), 1.89A and 2.75A (E21NK), 1.88A and 2.85A (Cooling), 2.85A 
and 3.57A (Heating) (E24/28NK). 
o  During Cooling and Soft Dry operations: 
Indoor suction temperature - indoor piping temperature is below 4°C. 
o  During Heating operations : 
Indoor piping temperature - indoor suction is under 5°C. 
 Control contents 
o  Compressor stops (and restart after 3 minutes). 
o  If the conditions above happen 2 times within 20 minutes, the unit will: 
 Stop operation 
  Timer LED blinks and “F91” indicated. 
 
14.1.6 Low Frequency Protection Control 1 
  When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency 
will be changed to 23 Hz for 2 minutes.