9.7. Protection Control
9.7.1. Outdoor Low-pressure Protection Control
The purpose of low-pressure protection control is gas leakage detection control.
The low-pressure protection control starts when low-pressure switch is activated less than 15 minutes after compressor startup.
During this protection control, compressor is shut down, indoor unit is set to thermo-off status.
After 6 occasions, suction pressure error is displayed; all operation stopped except outdoor fan remaining heat removal control.
9.7.2. Outdoor High-pressure Protection Control
The high-pressure protection control starts when high-pressure switch is activated less than 15 minutes after compressor star-
tup.
During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
After 6 occasions, high-pressure protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.7.3. Discharge Temperature Protection Control
The discharge temperature protection control starts when abnormal compressor temperature 115°C is detected when outdoor
unit is operating in cooling operation.
During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
After 6 occasions, high-pressure protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.7.4. Over Current Protection Control
The purpose of over current protection control is to protect the air conditioner from over current.
The over current protection control starts when input current from CT is maintained at 20A or more for 2 seconds when the out-
door unit is starting up or during cooling operation.
During this protection control, compressor is shut down. And indoor unit is set to thermo-off status.
After 4 occasions, over current protection error is displayed; all operation stopped except outdoor fan remaining heat removal
control.
9.7.5. CT Disconnection Detection Control
CT disconnection detection control detects if the CT sensor works normally.
The CT disconnection detection activates when:
- CT input value is maintained at compressor shutdown status (1.5A or less) consecutively for 2 seconds when the compressor
is operating.
- During this condition, compressor is shut down and indoor unit is set to thermo-off status.
- After 4 occasions, CT sensor error is displayed; all operation stopped except outdoor fan remaining heat removal control.
- CT input value is maintained at compressor operation status (5A or more) consecutively for a period of 60 seconds when the
compressor is shut down.
- During this condition, CT sensor error is displayed.
9.7.6. Connection Capacity Protection Control
The purpose of connection capacity protection control is to ensure the total capacity of connected indoor units is within accept-
able range.
During this protection control, connection capacity error is displayed; all operations stopped.
9.7.7. Sensor Disconnection Detection Control
The sensor disconnection detection control activates when the following condition comply:
During sensor disconnection, sensor error is displayed; all operations stops except outdoor fan remaining heat removal control.
Model Number Min. Capacity (kW) Max. Capacity (kW) Model Number Min. Capacity (kW) Max. Capacity (kW)
CU-J14DBE5 5.3 6.9 CU-J28DBE8 6.3 9.8
CU-J18DBE5 5.3 6.9 CU-J34DBE8 7.3 12.3
CU-J24DBE5 5.3 6.9 CU-J43DBE8 10.2 13.8
CU-J28DBE5 6.3 9.8 CU-J50DBE8 12.7 15.8
CU-J34DBE5 7.3 12.3
Sensor Detection Threshold Duration (Sec) Detection Condition
Discharge Temperature < -4.5°C or 201.8°C 5 Other than compressor start control
and compressor ON
Outdoor Heat Exchanger < -50.5°C or 103.7°C 5 Regularly