2. Installation work
a. Brazing work
Brazing work needs replacing air inside pipe with nitrogen gas in order to prevent oxidation scale from occurring. This
is called nitrogen replacement, and one of very important work in brazing refrigerant piping. (Oxidation preventive is
not possible to use)
b. Prevention measure for refrigerant piping
Prevention measure for refrigerant piping is very important work to prevent water-dust-rubbish from getting in. All pip-
ing terminals needs sealing such as shown below.
How to pinch
Close terminal part of piping with pliers and seal the gap with brazing.
How to tape
Seal terminal part of piping with vinyl tape.
3. Vacuum pumping
The purpose of vacuum pumping work is to remove and dry air inside the piping or nitrogen at air tightness test.
Perform the work carefully.
Place Period of work Method of seal
Outside More than 1 month Pinch
Less than 1 month Pinch or taping
Inside Not specified
Caution
Use the vacuum pump with the backflow prevention mechanism to prevent backflow of oil.
Vacuuming time 60 minutes or more Vacuum pump capacity
60 l/min or more

Table of Contents

Other manuals for Panasonic CS-F14DB4E5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-F14DB4E5 and is the answer not in the manual?

Panasonic CS-F14DB4E5 Specifications

General IconGeneral
BrandPanasonic
ModelCS-F14DB4E5
CategoryAir Conditioner
LanguageEnglish

Related product manuals