EasyManua.ls Logo

Panasonic CS-F28DTE5

Panasonic CS-F28DTE5
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
112
TC: Cooling Capacity IPT: Cooling Power Consumption
Model Cooling capacities are based on conditions
CS-F34DTE5 3 phase, 50Hz 400V
Cooling capacity Indoor temp. 27°C D.B. 19°C W.B.
10.0kW Outdoor temp. 35°C D.B.
Standard air volume 29 m
3
/min
Ambient Temperature Air Entering Condenser (°C D.B.)
Return 25°C30°C35°C40°C43°C
Air TCTCTCTCTC
D.B. W.B. kW kW kW kW kW
17 10.41 10.00 9.41 8.70 8.19
23 19 10.99 10.65 10.11 9.42 8.94
22 12.00 11.68 11.15 10.43 9.94
17 10.29 9.89 9.32 8.64 8.15
25 19 11.01 10.63 10.05 9.36 8.87
22 12.00 11.63 11.06 10.31 9.84
17 10.16 9.77 9.22 8.57 8.11
27 19 11.02 10.60 10.00 9.30 8.80
22 11.99 11.59 10.98 10.20 9.75
17 10.14 9.77 9.20 8.64 8.21
29 19 11.00 10.60 10.00 9.37 8.91
22 11.94 11.53 10.91 10.21 9.74
17 10.12 9.78 8.55 8.69 8.28
32 19 10.98 10.60 10.01 9.42 8.98
22 11.91 11.50 10.90 10.22 9.74
Ambient Temperature Air Entering Condenser (°C D.B.)
Return 25°C30°C35°C40°C43°C
Air IPT IPT IPT IPT IPT
D.B. W.B. kW kW kW kW kW
17 3.10 3.35 3.65 4.01 4.25
23 19 3.28 3.55 3.87 4.25 4.50
22 3.54 3.84 4.18 4.59 4.86
17 3.10 3.35 3.65 3.98 4.22
25 19 3.30 3.56 3.88 4.24 4.49
22 3.56 3.85 4.19 4.58 4.85
17 3.10 3.35 3.64 3.96 4.19
27 19 3.32 3.57 3.89 4.23 4.48
22 3.58 3.86 4.20 4.57 4.84
17 3.09 3.34 3.60 3.86 4.03
29 19 3.30 3.57 3.84 4.13 4.30
22 3.63 3.93 4.23 4.55 4.74
17 3.07 3.33 3.57 3.80 3.91
32 19 3.28 3.56 3.81 4.06 4.18
22 3.66 3.98 4.26 4.53 4.67