– 18 –
MAC9509078C2
CS-G93KE
2. COOLING OPERATION
A. Room Temperature Control
(i) When the remote control setting temperature is less than 24°C.
Operation Details
Cooling
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Outdoor Air Temperature
Model No.
+1.5
+1.0
+0.5
0
–0.5
–1.0
64 (Fc max) or 50
36
31
15
15
15
Comp OFF
Less than 38°C
Compressor Operation Frequency (Hz)
92 (Fc max) or 70
44
31
16
15
15
Comp OFF
Less than 38°C
64 (Fc max) or 50
40
31
22
15
15
Comp OFF
38°C and above
92 (Fc max) or 70
49
31
22
16
15
Comp OFF
38°C and above
CS-G93KE CS-G123KE
(ii) When the remote control setting temperature is 24°C and above.
Cooling
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Outdoor Air Temperature
Model No.
+1.5
+1.0
+0.5
0
–0.5
–1.0
64 (Fc max) or 50
36
31
15
15
15
Comp OFF
Less than 38°C
Compressor Operation Frequency (Hz)
92 (Fc max) or 70
44
31
16
15
15
Comp OFF
Less than 38°C
64 (Fc max) or 50
36
31
15
15
15
Comp OFF
38°C and above
92 (Fc max) or 70
44
31
16
15
15
Comp OFF
38°C and above
CS-G93KE
Compressor OFF temperature = Compressor ON temperature.
The operation frequency can be changed every 30 seconds.
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
The compressor stops when the intake air temperature reaches 1°C below internal setting temperature and
continues for 3 minutes.
When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
When the compressor stops, the outdoor fan motor stops 30 seconds later.
CS-G123KE
Untitled-3 6/20/00, 5:03 PM18