● Measure the electric current
during operation
● Measure the gas side pressure
● Measure the air temperature
difference
Servicing Information
Lower than specified
Cooling Mode
Low
Low
Low
Low
Low
High
2. TROUBLESHOOTING AIR CONDITIONER
Refrigeration cycle system
In order to diagnose malfunctions, make sure that
there are no electrical problems before inspect-
ing the refrigeration cycle. Such problems include
insufficient insulation, problem with the power source,
malfunction of a compressor or a fan.
The normal outlet air temperature and pressure
of the refrigeration cycle depends on various condi-
tions; the standard values for them are shown in the
table on the right.
Normal Pressure and Outlet Air Temperature (Standard)
Outlet air
temperature (°C)
12 ~ 16
36 ~ 45
★ Condition: • Indoor fan speed; High.
• Outdoor temperature is 35°C at cooling
mode and 7°C at heating mode.
• Compressor operates at rated frequency.
Cooling mode
Heating Mode
Gas pressure
MPa (kg/cm
2
G)
0.4 ~ 0.6 (4 ~ 6)
1.5 ~ 2.1 (15 ~ 21)
Inefficient compressor
Insufficient refrigerant
Inefficient compressor
Insufficient refrigerant
Clogged strainer or
capillary tube
Clogged strainer or
capillary tube
Difference in the intake
and outlet
air temperatures
Value of electric
current during operation
Normal
Excessive amount
of refrigerant
Dusty condenser
preventing heat radiation
Above 8°C
(15 minutes after an
operation is started.)
at cooling mode
Above 14°C
(15 minutes after an
operation is started.)
at heating mode
Less than 8°C at cooling mode
Less than 14°C at heating mode