– 20  –
MAC9509078C2
CS-G93KE
Operation Details
3. SOFT DRY OPERATION
A. Room Temperature Control
At the start of operation, cooling operation is running until the intake air temperature is 0.5°C higher than internal
setting temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.
Soft Dry
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Condition
Model No.
+1.5
+1.0
+0.5
0
–0.5
–3.5
Cooling Operation
15
15
15
Comp OFF
When the
temperature falls
Compressor Operation Frequency (Hz)
Cooling Operation
16
15
15
Comp OFF
When the
temperature falls
22
22
16
15
15
Comp OFF
When the
temperature rises
• Compressor OFF temperature = Compressor ON temperature.
• The operation frequency changes every 30 seconds.
• 30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
• The Compressor stops when the intake air temperature reaches 3.5°C below internal setting temperature and continues
for 3 minutes.
• When the compressor stops operation, indoor fan stops for 330 seconds.
• When the Compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
• When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation
immediately.
• When the Compressor stops, the outdoor fan motor stops 30 seconds later.
22
22
15
15
15
Comp OFF
When the
temperature rises
CS-G93KE CS-G123KE
Untitled-3 6/20/00, 5:03 PM20