12.10   Freeze Prevention Control 
•  When indoor heat exchanger temperature is lower than 32°F continuously for 6 minutes, compressor will stops 
operation. 
•  Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 55.4°F. 
•  At the same time, indoor fan speed will be higher than during its normal operation. 
•  If the indoor heat exchanger temperature is higher than 55.4°F for 5 minutes, the fan speed will return to its 
normal operation. 
 
12.11   Freeze Prevention Control 2 
•  Control start conditions 
o  During Cooling operation and soft dry operation 
  During thermo OFF condition, indoor intake temperature is less than 50°F or  
  Compressor stops for freeze prevention control 
o  Either one of the conditions above occurs 5 times in 60 minutes. 
• Control contents 
o Operation stops 
o  Timer LED blinks and “H99” indicated 
 
12.12   Dew Prevention Control 
•  To prevent dew formation at indoor unit discharge area. 
•  This control will be activated if: 
o  Outdoor air temperature and indoor pipe temperature judgment by micro controller is fulfilled. 
o  When cooling or dry mode is operated more than 20 minutes. 
•  This control stopped if: 
o Compressor stopped. 
o  Remote control setting changed (fan speed/temperature). 
o  Outdoor air temperature and indoor intake temperature changed. 
•  Fan speed, angle of louver (vertical airflow angle) will be adjusted accordingly in this control. 
o  Fan speed will be increased slowly when control is activated until predetermine value. 
• Compressor frequency will be regulated accordingly.