14.3  Error Code Table 
Diagnosis 
display 
Abnormality / Protection control  Abnormality Judgment
Emergency 
Operation 
Primary location to verify 
H00  No abnormality detected  -  Normal operation   
H11 
Indoor / Outdoor abnormal 
communication 
> 1 min after starting 
operation 
Indoor fan operation 
only 
•  Internal / external cable connection 
•  Indoor / outdoor PCB 
H12  Connection capability rank abnormality 
Continuously for 90 sec 
after power supplied 
- - 
H14 
Indoor intake air temperature sensor 
abnormality 
Continue for 5 sec.  - 
•  Intake air temperature sensor 
(defective or disconnected) 
H15 
Outdoor compressor temperature sensor 
abnormality 
Continue for 5 sec.  - 
•  Compressor temperature sensor 
(defective or disconnected) 
H16  Outdoor current transformer open circuit  -  - 
• Outdoor PCB 
•  IPM (Power transistor) module 
H19  Indoor fan motor mechanism locked 
7 occurrences 
continuously 
- 
• Indoor PCB 
• Fan motor 
H23 
Indoor heat exchanger temperature 
sensor abnormality 
Continue for 5 sec. 
○ 
 
•  Heat exchanger temperature sensor 
(defective or disconnected) 
H27 
Outdoor air temperature sensor 
abnormality 
Continue for 5 sec. 
○ 
 
•  Outdoor temperature sensor 
(defective or disconnected) 
H28 
Outdoor heat exchanger temperature 
sensor abnormality 
Continue for 5 sec. 
○ 
 
•  Outdoor heat exchanger 
temperature sensor (defective or 
disconnected) 
H30 
Discharge temperature sensor 
abnormality 
Continue for 5 sec.   
•  Outdoor discharge temperature 
sensor (defective or disconnected) 
H33  Indoor / outdoor wrong connection  -  - 
•  Indoor / outdoor supply voltage 
H38  Indoor / outdoor mismatch (brand code)  -  -  - 
H64 
Outdoor high pressure sensor 
abnormality 
Continue for 1 minutes  - 
  Lead wire and connector 
H97 
Outdoor fan lock abnormality 
 
2 occurrences within 30 
minutes 
 
  Outdoor fan motor locked 
H98  Indoor temperature rise abnormality  -  - 
  Air circulation short circuit 
H99 
Indoor heat exchanger freeze prevention 
protection 
- - 
  Air filter dirty 
F11  4 way valve switching failure * 
4 occurrences within 30 
minutes 
- 
 v-coil 
F17  Indoor standby units freezing abnormality 
3 times happen within 
40 minutes 
- 
  Check indoor/outdoor connection 
wire and pipe 
  Indoor heat exchanger sensor lead 
wire and connector 
  Expansion valve lead wire and 
connector. 
F90 
System and compressor microcomputer 
communication error(for S10*** only)  
2 occurrences within 5 
seconds 
- 
 Outdoor PCB 
F90  Power factor correction abnormality  
4 occurrences within 20 
minutes 
- 
 Outdoor PCB 
F91  Refrigerant cycle abnormal 
2 occurrences within 20 
minutes 
- 
  No refrigerant ( 3-way valve is 
closed) 
F93  Outdoor compressor abnormal revolution 
4 occurrences within 20 
minutes 
- 
 Outdoor compressor 
F95  Cooling high pressure protection 
4 occurrences within 20 
minutes 
- 
  Outdoor refrigerant circuit 
F96 
Intelligent power transistor overheating 
protection 
- - 
  IPM (Power transistor) 
F97 
Compressor temperature rise protection 
control 
4 times occurrence within 
20 minutes 
- 
 Compressor 
F98  Total running current protection 
3 times occurrence within 
20 minutes 
- 
  Improper heat radiation 
F99 
Outdoor direct current (DC) peak 
detection 
7 times occurrence 
continuously 
- 
 Compressor 
Note: 
“○” – Frequency measured and fan speed fixed 
“ * ”– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has 
abnormality. 
 
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” 
sound heard following by pressing the CHECK button at remote control. 
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors 
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote 
control signal receiving sound is changed from one “beep” to four “beep” sounds.