115 
18.4.24    F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) 
Malfunction Decision Conditions 
  During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by 
the outdoor unit heat exchanger thermistor. 
 
Malfunction Caused 
  Outdoor heat exchanger temperature rise due to short-circuit of hot discharge air flow. 
  Outdoor heat exchanger temperature rise due to defective of outdoor fan motor. 
  Outdoor heat exchange temperature rise due to defective outdoor heat exchanger thermistor. 
  Outdoor heat exchanger temperature rise due to defective of outdoor unit PCB. 
 
Troubleshooting