25.3. Heating mode operation time chart (Heat pump type only)
(*2)
Outdoor unit fan control during heating mode operation
Under conditions when the compressor is on during heating mode operation (except during defrosting and
when the liquid bypass valve is on), the outdoor unit fan is controlled by means of input (CN2) indicating
whether the contact of the heating pressure switch on the outdoor unit circuit board is open or closed
(At the start of heating mode operation, the fan operates at HI speed.)
87