25.4. Hot starting
1. When heating mode operation starts
1. Start
Hot start control commences heating mode operation starts.
2. Operation
“PREHEAT” appears on the remote control display. (Other displays remain unchanged.)
At the indoor unit, the indoor unit fan stops. In addition, during hot starting, the louvre stays at the horizontal
position (angle 0°).
3. Cancelling
After 1 minute has passed since heating mode operation started, or if the compressor has turned on, hot
starting is cancelled when the temperature detected by the indoor unit pipe temperature sensor is 18°C
or higher.
After cancellation, the “PREHEAT” display on the remote control disappears and the louvre operation
returns to the previous setting.
(However, for 2 minutes after cancellation, the indoor unit fan operates at LOW speed, and then returns to
the previous setting.)
<When hot start operation is cancelled by temperature>
2. When defrosting is complete
1. Start
Hot start control commences when defrosting is complete.
2. Operation
“PREHEAT” appears on the remote control display. (Other displays remain unchanged.)
At the indoor unit, the indoor unit fan stops. In addition, during hot starting, the louvre stays at the horizontal
position (angle 0°).
88

Other manuals for Panasonic CS-W24BD2P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-W24BD2P and is the answer not in the manual?

Panasonic CS-W24BD2P Specifications

General IconGeneral
BrandPanasonic
ModelCS-W24BD2P
CategoryAir Conditioner
LanguageEnglish

Related product manuals