97
14.14.1.9 Rhythmic Temperature Wave Operation
To further maximize the energy saving during ECONAVI operates at low activity level.
Start condition
o The unit is operates in Cool or Dry mode under ECONAVI operation, and
o Human activity sensor detects low activity level continuously for 60 minutes, and
Stop condition
o Unit is off, or
o ECONAVI is off, or
o Human activity sensor detects high activity level or absent, or
Control contents
o When all start conditions complied, set temperature will shift accordingly as following:
Low activity Normal activity
Human
Mode
Set
temperature
High activity Absent
ECONAVI ; Detecting human presence and activity, the unit controls room temperature to save energy.
ECONAVI take advantage of the human nature that
human being takes time to feel the temperature rise
during low activity level; the unit adjusts temperature to
maximise energy saving without sacrificing the comfort.
HEAT
COOL/DRY
-2 °C-2 °C
Low activity
Human
Mode
Precise control of temperature during low activity to maximise energy saving.
Set
temperature
COOL/DRY
ECONAVI
+2 °C
+1 °C