16
Model
Indoor CS-Z25XKEW, CS-XZ25XKEW
Outdoor CU-Z25XKE
Performance Test Condition EUROVENT
Power Supply
Phase, Hz Single, 50
V 230
Min. Mid. Max
Cooling
Capacity
kW 0.85 2.50 3.50
BTU/h 2900 8530 11900
kcal/h 730 2150 3010
Running Current A - 2.40 -
Input Power W 170 510 900
Annual Consumption kWh - 255 -
EER Class - A -
EER
W/W 5.00 4.90 3.89
BTU/hW 17.06 16.73 13.22
kcal/hW 4.29 4.22 3.34
ErP
Pdesign kW 2.5
SEER (W/W) 9.4
Annual Consumption kWh 93
Class A+++
Power Factor % - 92 -
Indoor Noise (H / L / QLo)
dB (A) 39 / 25 / 19
Power Level dB (A) 55 / - / -
Outdoor Noise (H / L / QLo)
dB (A) 46 / - / -
Power Level dB (A) 61 / - / -
Heating
Capacity
kW 0.80 3.40 4.80
BTU/h 2730 11600 16400
kcal/h 690 2920 4130
Running Current A - 3.20 -
Input Power W 160 700 1.18k
COP CLASS - A -
COP
W/W 5.00 4.86 4.07
BTU/hW 17.06 16.57 13.90
kcal/hW 4.31 4.17 3.50
ErP
Pdesign kW 2.4
Tbivalent °C -10
SCOP (W/W) 5.2
Annual Consumption kWh 646
Class A+++
Power Factor % - 95 -
Indoor Noise (H / L / QLo)
dB (A) 41 / 27 / 19
Power Level dB (A) 57 / - / -
Outdoor Noise (H / L / QLo)
dB (A) 47 / - / -
Power Level dB (A) 62 / - / -
LOW Temp: Capacity (kW) / I. Power W) / COP 3.48 / 1.04k / 3.35
EXTR LOW Temp: Capacity (kW) / I. Power W) / COP 2.80 / 1.00k / 2.80
Max Current (A) / Max Input Power (W) 5.3 / 1.18k
Starting Current (A) 3.20