22
Multi Split Combination Possibility:
o A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE, CU-4E27PBE.
o A single outdoor unit enables air conditioning of up to five separate rooms for CU-5E34PBE.
CONNECTABLE INDOOR UNIT CU-4E23PBE CU-4E27PBE CU-5E34PBE
ROOM A B C D A B C D A B C D E
Wall
1.6kW CS-MZ16TKE
2.0kW
CS-Z20TKEW
CS-XZ20TKEW
2.5kW
CS-Z25TKEW
CS-XZ25TKEW
3.5kW
CS-Z35TKEW
CS-XZ35TKEW
4.2kW CS-Z42TKEW
5.0kW
CS-Z50TKEW
CS-XZ50TKEW
7.1kW CS-Z71TKEW – – – –
Capacity range of connectable units From 4.8kW to 11.0kW From 4.8kW to 13.6kW From 4.8kW to 17.5kW
Pipe length
1 room maximum pipe length (m) 25 25 25
Allowable elevation (m) 15 15 15
Total allowable pipe length (m) 70 70 80
Total pipe length for maximum
chargeless length (m)
40 45 45
Additional gas amount over
chargeless length (g/m)
20 20 20
Note: “” : Available
Remarks for CU-4E23PBE / CU-4E27PBE / CU-5E34PBE
1. The total nominal cooling capacity of indoor unit that will be connected to outdoor unit must be within connectable capacity range of indoor
unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-4E27PBE. (Total nominal capacity of indoor units is between
4.5kW to 13.6kW)
1) Two CS-Z25TKEW only. (Total nominal cooling capacity is 5.0kW)
AMP Air Conditioning