15.3 Piping Length Correction Factor
The characteristic of the unit has to be corrected in accordance with the piping length.
Note: The graphs show the factor after added right amount of additional refrigerant.
Maximum piping length for Z50XKEW is 20 meters.
Maximum piping length for Z71XKEW is 30 meters.
Cooling Capacity
3
1.0159
5
1.0000
10 0.9889
15 0.9800
20 0.9746
30
0.951634
Heating Capacity
3
1.0056
5
1.0000
10 0.9931
15 0.9828
20 0.9741
30
0.9677
Cooling Capacity
Correction Factor
Pipe Length (m)
0.95
0.97
0.99
1.01
1.03
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32
Heating Capacity
Correction Factor
Pipe Length (m)
0.96
0.97
0.97
0.98
0.98
0.99
0.99
1.00
1.00
1.01
1.01
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32