Table (b): Outdoor Air Temperature Shifting
Mode: Outdoor Temperature, X (°C): Temperature Shift (°C)
Manual Operation Auto Operation
Cooling/Soft Dry 38 X 1.50 2.00
30 X 38 1.25 1.25
23 X 30 1.25 1.25
X 23 1.75 1.75
Heating 21 X -2.25 -1.50
17 X 21 -1.75 -1.00
13 X 17 -0.75 0.00
9 X 13 0.25 0.25
5 X 9 1.25 1.00
1 X 5 0.75 1.00
-3 X 1 1.50 1.00
X -3 1.50 1.00
Table (c): Powerful Mode Shifting
Mode: Period, X (min): Temperature Shift (°C)
Cooling X 20 -2.0
X 20 0.0
Soft Dry X 20 -1.0
X 20 0.0
Heating X 20 +3.5
X 20 +3.25
Table (d): Quiet (Lo) Mode Shifting
Mode: Period, X (min): Temperature Shift (°C)
Cooling, Soft Dry 20 min X 50 min -3.0
50 min X 110 min -4.0
110 min X 440 min -5.0
Table (e): Fan Speed Shifting
Mode: Fan Speed: Temperature Shift (°C)
Cooling Lo -0.25
Me-, Me, Me+, Auto 0.00
Hi +0.25
Soft Dry All +0.25
Heating Lo +1.50
Me-, Me, Me+, Auto +0.75
Hi +0.75
Table (f): Start-Up Shifting
Mode within 60 Minutes from Start-up: Temperature Shift (°C)
Cooling/Soft Dry -1.0
Heating +2.0