51 
[Heating] 
  According to indoor pipe temperature, automatic heating fan speed is determined as follows. 
 
 
 
B. Feedback control 
  Immediately after the fan motor started, feedback control is performed once every second. 
  During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error 
counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan 
motor error is detected. Operation stops and cannot on back. 
 
12.3  Outdoor Fan Motor Operation 
Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 
30 seconds after compressor stops operation. 
 
 
 
12.4 Airflow Direction 
  There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by 
vertical vanes). 
  Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat 
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using 
remote control). 
12.4.1 Vertical Airflow 
Vane Angle (°) : E7/9/12/15NK  Vane Angle (°) : E18NK 
Operation Mode  Airflow Direction 
1 2 3 4 5 1 2 3 4 5 
A 10 
5 
B 43.8 
30 
Auto with Heat Exchanger 
Temperature 
C 21.2 
17.5 
Heating 
Manual  10  21.2 32.5 43.8  55 
5  17.5 30 42.5 55 
Auto  10 ~ 40 
5 ~ 35 
Cooling 
Manual  10 17.5 25 32.5 40 
5  12.5 20 27.5 35 
Auto  10 ~ 40 
5 ~ 35 
Soft Dry 
Manual  10 17.5 25 32.5 40 
5  12.5 20 27.5 35 
 
1  Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the 
angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat 
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner 
is stopped using remote control, the vane will shift to close position.