54 
12.8.1 ON Timer Control 
  ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier than 
the setting time. 
This is to provide a comfortable environment when reaching the set ON time. 
  60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to 
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting 
time. 
  From the above judgment, the decided operation will start operate earlier than the set time as shown below. 
 
 
 
12.8.2  OFF Timer Control 
OFF timer 1 and OFF timer 2 can be set using remote control, the unit with timer set will stop operate at set time. 
 
12.9 Auto Restart Control 
1  When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within 
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be 
selected randomly) after power supply resumes. 
2  This type of control is not applicable during ON/OFF Timer setting. 
3  This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board. 
12.10   Indication Panel  
LED POWER  TIMER  POWERFUL  QUIET ECONAVI AUTO COMFORT nanoe-G 
Color Green  Orange  Orange  Green  Green  Green  Blue 
Light ON  Operation ON  Timer Setting ON 
POWERFUL Mode 
ON 
QUIET Mode 
ON 
ECONAVI ON
AUTO COMFORT 
ON 
nanoe-G ON 
Light OFF  Operation OFF Timer Setting OFF 
POWERFUL Mode 
OFF 
QUIET Mode 
OFF 
ECONAVI OFF
AUTO COMFORT 
OFF 
nanoe-G OFF
 
Note: 
  If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation 
mode judgment, or ON timer sampling. 
  If Timer LED is blinking, there is an abnormality operation occurs.