9.4. Heating Mode Operation
9.3.6. Drain pump control
During cooling, dry, or defrost operation, drain pump operate by following the below table.
When compressor start, drain pump operation start after 10 second of indoor fan starting.
When operation stop or thermostat is off, drain pump continue operating for 6 minute to prevent the drain water from coming
back.
9.3.7. Cooling low temperature protection control
During cooling, or dry operation, if outdoor temperature is less than -15°C.
And thermostat on condition continue for 15 min, compressor stop.
After 3 min waiting (restart delay), if thermostat is on, compressor restart.
9.4.1. Heating indoor fan control
Fan speed manual
Fan speed [Hi] [Me] [Lo] set by remote controller.
However, when operation start, or during operation, fan speed control is limited to due to prevent a cold draft, for example, when
heating operation start.
(K10 = Indoor heat exchanger temperature, depend on indoor type)