9 Operation Details
9.1. Fan Mode Operation
Fan operation only. Fan in operation according to Remote Control or Main Unit (Touch Control Panel) setting.
9.1.1. Manual Setting of Fan Speed
Basic Fan Speed can be manually adjusted (Lo or Hi) by using the Fan Speed Selection Button/Pad at Remote Control or Main
Unit (Touch Control Panel).
9.2. Cooling Mode Operation
Cooling in operation according to Remote Control or Main Unit (Touch Control Panel) setting.
9.2.1. Time Delay Safety Control (3 minute)
When the compressor is stopped by Operation Switch at the Remote Control or Main Unit (Touch Control Panel), it restart after
3 minutes when the Operation Switch at the Remote Control or Main Unit (Touch Control Panel) is turned ON.
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
Protection of compressor to balance the pressure in the refrigeration cycle for 3 minutes.
9.2.2. 7 minutes Time Saved Control
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
9.2.3. Starting Current Control
When the compressor and fan motor are simultaneously started, the fan motor will operate 1.6 seconds later.
9.2.4. Freeze Prevention Control
If the temperature of the indoor heat exchanger falls
continuously below 10°C for 3 minutes or more, the
compressor turns off to protect the heat exchanger from
freezing. The fan speed setting remains the same.
Compressor restarts when the heat exchanger temperature
rises to 12°C (Recovery).
*3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
9.2.5. Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and heat
exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically (Time Delay Safety Control is valid).
10
CW-XC100VK / CW-XC120VK