1-140
1
Simultaneous (Triple) -Type
1-1. Unit Specifi cations
PE1
6. 4-Way Cassette 60×60 Type S-50PY2E5A×3 / U-140PE1E8A
INDOOR MODEL S-50PY2E5A ×3
PANEL MODEL (CZ-KPY3A / CZ-KPY3B) ×3
OUTDOOR MODEL U-140PE1E8A
Branch pipe MODEL CZ-P3HPC2BM
PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 / EN12102
POWER SUPPLY
ø, Hz 1ø 50Hz 3ø 50Hz
V 220 230 240 380 400 415 Min Max
C
O
O
L
I
N
G
CAPACITY
kW 14.0 14.0 14.0 3.3 15.5
BTU/h 47800 47800 47800 11300 52900
CURRENT A 0.35 × 3 7.40 7.00 6.80 - -
INPUT POWER
W 45 × 3 4.565k 4.565k 4.565k - -
TOTAL W - 4.700k 4.700k 4.700k 840 6.000k
ANNUAL CONSUMPTION
TOTAL kWh
*
4 - - - - 2350 - - -
EER/EER CLASS
TOTAL(W/W)
*
5/("A"~"G")
- - - 2.98 2.98/C 2.98 3.93 2.58
Erp
*
6
Pdsign kW - - - - - -
SEER (W/W) - - - - - -
Annual consumption
kWh------
Class - - - - - -
POWER FACTOR % - - - 94 94 93
NOISE INDOOR
(H/M/L)
dB-A 40/37/33
Power Level dB 55/52/48
NOISE OUTDOOR
(H/L)
dB-A 54/-
Power Level dB 71/-
H
E
A
T
I
N
G
CAPACITY
kW 16.0 16.0 16.0 4.1 18.0
BTU/h 54600 54600 54600 14000 61400
CURRENT A 0.35 × 3 7.70 7.30 7.00 - -
INPUT POWER
W 40 × 3 4.700k 4.700k 4.700k - -
TOTAL W - 4.820k 4.820k 4.820k 900 5.900k
COP/COP CLASS
TOTAL(W/W)
*
5/("A"~"G")
- - - 3.32 3.32/C 3.32 4.56 3.05
Erp
*
6
Pdsign kW - - - - - -
Tbivalen °C - - - - - -
SCOP (W/W) - - - - - -
Annual consumption
kWh------
Class - - - - - -
POWER FACTOR % - - - 93 93 93
NOISE INDOOR
(H/M/L)
dB-A 40/37/33 -
Power Level dB 55/52/48 -
NOISE OUTDOOR
(H/L)
dB-A - 55/-
Power Level dB - 71/-
EXTRA LOW TEMP
Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W) 0.40/55 × 3 11.0/6.80k 11.0/7.15k 11.0/7.45k
STARTING CURRENT(A)/COMP OUTPUT(W) - - - 7.70/3.0k 7.30/3.0k 7.00/3.0k
NETWORK IMPEDANCE (ΩMAX.) - -
FM OUTPUT (W) 40 × 3 90 × 2
MOISTURE REMOVAL VOLUME L/h(Pt/h) 9.0 (3.0×3) (18.9) -
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min)
11.1×3/9.8×3/8.5×3 (392)×3/(346)×3/(300)×3
HEAT m
3
/min (ft
3
/min)
11.1×3/9.8×3/8.7×3 (392)×3/(346)×3/(307)×3
O/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 135 (4767)
HEAT m
3
/min (ft
3
/min) 120 (4238)
REFRIGERANT TYPE, AMOUNT
g
(oz) R410A 3.40k (119.9)
P
R
O
D
I
M
HEIGHT : H mm(inch) 260<265 + 23> (10-1/4) 1416 (55-3/4)
WIDTH : W mm(inch) 575<583> (22-21/32) 940 (37-1/32)
DEPTH : D mm(inch) 575<583> (22-21/32) 340 (13-13/32)
Panel : H×W×D mm 3A:31 × 700 × 700, 3B:31 × 625 × 625
-
P
A
C
D
I
M
HEIGHT : H mm 345 (13-19/32) 1556
WIDTH : W mm 691 (27-7/32) 1055
DEPTH : D mm 691 (27-7/32) 485
MASS
(NET) k
g
(lb) 18 (40) 98 (216)
(GROSS) k
g
(lb) 23 (51) 108 (238)
Panel : (NET) k
g
(lb) 2.4 (5.3) -
LAYERS LIMIT (actually) 11 (12) 1 (2)
Operation
Condition
Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C
Heat (DBT) 16°C ~ 30°C -20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
ared type, 5.0 (16.4) ared type, 5.0 (16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 75 (16.4 ~ 246.1)
I/D&O/D HEIGHT DIFFERENCE m (ft)
15(OD located lower)/30(OD located higher) (49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50 (0.538)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
20 (65.6)
*1: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2: If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7
°C
dry bulb and -8
°C
wet-bulb temperatures with rated voltage 230V
shall be used.
*3: Network Impedance shall be applicable for EUROPE and CHINA models.
*4: The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5: EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6: SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche
data indicates in an attached sheet.
SM830231-02Single.indb140SM830231-02Single欧州.indb140 2014/09/1913:21:112014/09/1913:21:11

Other manuals for Panasonic CZ-KPY3A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CZ-KPY3A series and is the answer not in the manual?

Panasonic CZ-KPY3A series Specifications

General IconGeneral
BrandPanasonic
ModelCZ-KPY3A series
CategoryAir Conditioner
LanguageEnglish

Related product manuals