77
<Procedure of CZ-RTC5B>
Fig. 7-4
1
Keep pressing the , and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the or button to see each
menu.
If you wish to see the next screen instantly, press
the or button.
Select “8. Detailed settings” on the LCD display
and press the button.
The “Detailed settings” screen appears on the
LCD display.
Select the “Unit no. by pressing the
or
button for changes.
3
Select the “Code no. by pressing the or
button.
Change the “Code no. by pressing the or
button (or keeping it pressed).
4
Select the “Set data” by pressing the or
button.
Select one of the “Set data” by pressing the
or button.
Then press the button.
5
Select the “Unit no. by pressing the or
button and press the button.
The “Exit detailed settings and restart?” (Detailed
setting-end) screen appears on the LCD display.
Select “YES” and press the button.
SM830255-00_Single_欧州4方向 TD&SM.indb 7 16/09/21 13:54:48
20:30 (THU)
START
[ ]
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Sel. Page [ ] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel. Page [ ] Confirm
20:30 (THU)
7. Simple settings
Detailed settings
Unit no. Code no. Set data
10
1-1 0001
Sel. Next
20:30 (THU)
Detailed settings
Unit no. Code no. Set data
1-1 0001
Sel. Next
20:30 (THU)
10
Detailed settings
Unit no. Code no. Set data
ALL
Sel. Next
20:30 (THU)
01 0002
Exit detailed settings
and restart?
NOYES
Detailed settings
Unit no. Code no. Set data
1-1
Sel.
20:30 (THU)
10 0001
[ ] Confirm
7-6