1-12-2-1-2
1
How to separate the indoor unit
1. Remove the wire cover.
(1)  Loosen two screws.
Two screws
(2)   Move to the left and remove the wire 
cover through the round hole.
Move to the left.
Remove the wire cover.
2. Remove the fan cover unit.
(1)  Loosen four screws.
Four screws
Fan cover unit
(2)   Move the fan cover unit upward and 
remove it through the round hole.
3. Remove the motor relay connector.
Remove two motor relay connectors.
Remove the wire from the fixed mounting bracket.
4. Separate the fan motor unit and heat 
exchanger unit.
(1)   Loose the upper side three bolts and 
remove the lower side three bolts.
WARNING
Do not remove the upper side three bolts.
The motor unit may drop during work of 
unit separation and can lead to personal 
injury or death.
Loosen the upper side three bolts.
Remove the lower side three bolts.
(2)   Move upward and remove the fan motor 
unit through the round hole.
How to assemble the indoor unit 
1. Attach the fan motor unit.
(1)   Pass the bolts for the heat exchanger 
unit through the round holes.
Mount the unit with three holes located 
in the center of the upper side.
(2)   Attach three bolts in the lower side and 
then fasten three bolts in the upper side. 
(Tightening torque : 2.45 ~ 3.4 N · m)
Attach three bolts.
Fasten three bolts.
(3)   Attach the motor wire.
Wire with the fixed mounting bracket.
Attach two motor connectors.
(Connectors at each end should be 
matched with the same color.)
2.  Attach the fan cover unit and wire cover. 
Attach the fan cover unit and wire cover in 
reverse order of separating unit.
SM830276-00_欧州向け R32シングル TD&SM.indb   2 2019/02/27   11:54:43