How to set the external static pressure
1. Keep pressing the , and buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD display.
2. Press the or button to see beach menu. If
you wish to see the next screen instantly, press the
or button.
Select “8. Detailed settings” on the LCD display and press the
button.
The “Detailed settings” screen appears on the LCD display.
Select the “Unit no.” by pressing the or button
for changes.
,
Maintenance func
0. ECONAVI info.
1. Outdoor unit error data
2. Service contact
3. RC setting mode
Sel. Page [ ] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Sel. Page [ ] Confirm
20:30 (THU)
Detailed settings
Unit no. Code no. Set data
10
3-1 0006
Sel. Next
20:30 (THU)
3. Select the “Code no.” by pressing the or
button.
Change the “Code no.” to “5D” by pressing the or
button (or keeping it pressed).
4. Select the “Set data” by pressing the or
button.
Select one of the “Set data” among “0006”, “0003” or “0001”
according to the desired external static pressure setting by
pressing the or button.
(See Table 1-12-2-1-4 and Fig. 1-12-2-1-4.)
Then press the button.
5. Select the “Unit no.” by pressing the or
button and press the button.
The “Exit detailed settings and restart?”
(Detailed setting-end) screen appears on the LCD display.
Select “YES” and press the button.
Detailed settings
Unit no. Code no. Set data
10001-3
Sel. Next
20:30 (THU)
5D
Table 1-12-2-1-4 Setting the external static pressure
Indoor unit Item code
200 250
5D
External static pressure of the rated
air flow volume
180 Pa 200 Pa 0006
120 Pa 130 Pa 0003
75 Pa 75 Pa 0001
Detailed settings
Unit no. Code no. Set data
10
1-1 0001
Sel. Next
20:30 (THU)
Exit detailed settings
and restart?
NOYES