1-1-1-1-8
1
Double Twin-Type
1-1. Unit Specications
PZH2
4-Way Cassette Type S-60PU2E5B ×4 / U-250PZH2E8
INDOOR MODEL S-60PU2E5B ×4 - -
PANEL MODEL
Standard type:CZ-KPU3 / ECONAVI type:CZ-KPU3A
- -
OUTDOOR MODEL - U-250PZH2E8 -
Branch pipe MODEL CZ-P680BK2 + CZ-P155BK1×2
Performance test condition ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz 1Ø 50Hz 3Ø 50Hz
V 220V 230V 240V 380V 400V 415V Min Max
C
O
O
L
I
N
G
Capacity
kW 25.0 25.0 25.0 - - - 6.1 28.0
BTU/h 85300 85300 85300 - - - 20800 95500
Current A 0.36 ×4 0.35 ×4 0.34 ×4 12.9 12.2 11.8 - -
Input power
W 38 ×4 38 ×4 38 ×4 7.908k 7.908k 7.908k - -
TOTAL W - 8.060k 8.060k 8.060k 1.200k 9.720k
Annual consumption TOTAL kWh *
4
- - - - 4030 - - -
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.10 3.10 /B 3.10 5.08 2.88
Erp
*
6
Pdesign kW - - - - 25.0 - - -
η
s,c
(W/W) - - - - 296.2 - - -
Annual consumption
kWh - - - - - - - -
Class - - - - - - - -
Power factor % - - - 93 93 93 - -
Noise indoor *
7
dB-A (H/M/L) 36/31/28 - - -
Power Level dB 51/46/43 - - -
Noise outdoor
dB-A (H/L) - 59/- - -
Power Level dB - 78/- - -
H
E
A
T
I
N
G
Capacity
kW 28.0 28.0 28.0 - - - 5.5 31.5
BTU/h 95500 95500 95500 - - - 18800 107500
Current A 0.35 ×4 0.34 ×4 0.33 ×4 11.5 10.9 10.5 - -
Input power
W 36 ×4 36 ×4 36 ×4 7.056k 7.056k 7.056k - -
TOTAL W - 7.200k 7.200k 7.200k 1.000k 10.100k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.89 3.89 /A 3.89 5.50 3.12
Erp
*
6
Pdesign at -10°C kW - - - - 20.0 - - -
Tbivalent °C - - - - -10 - - -
η
s,h
(W/W) - - - - 174.1 - - -
Annual consumption
kWh - - - - - - - -
elbu(-10°C) kW - - - - 0.00 - - -
Class - - - - - - - -
Power factor % - - - 93 93 93 - -
Noise indoor *
7
dB-A (H/M/L) 36/31/28 - - -
Power Level dB 51/46/43 - - -
Noise outdoor
dB-A (H/L) - 63/- - -
Power Level dB - 82/- - -
EXTRA LOW TEMP
Total capacity(kW)/Input power(W)/COP
- -
Max Current(A) / Max Input power(W) 0.36/38 ×4 0.35/38 ×4 0.34/38 ×4 18.5/11.3k 18.5/11.9k 18.5/12.4k -
Starting current(A) (Cooling/Heating) - - - 12.9/11.5 12.2/10.9 11.8/10.5 -
Comp output(W) - 5.50k 5.50k 5.50k -
Time Delay fuse max size(A) 5 30 -
Network Impedance(ΩMAX.) - - -
Fan motor output (Indoor/Outdoor) W 60 120 × 2 -
Moisture removal volume
L/h(Pt/h)
6.8 (1.7 ×4) (14.3) - -
External static pressure Pa - - -
Indoor
Air ow *
7
Cooling
m
3
/min (m
3
/h) (H/M/L)
21.0×4/16.0×4/13.0×4 (1260)×4/(960)×4/(780)×4
- - -
Heating
m
3
/min (m
3
/h) (H/M/L)
21.0×4/16.0×4/13.0×4 (1260)×4/(960)×4/(780)×4
- - -
Outdoor
Air ow
Cooling m
3
/min (m
3
/h) - 160.0 (9600) - -
Heating m
3
/min (m
3
/h) - 160.0 (9600) - -
Refrigerant type / amount
g
(oz) - R32 5.20k (183.4) -
Product dimension
Height
mm(inch)
256 (10-5/64) 1500 (59-1/16) -
Width
mm(inch)
840 (33-5/64) 980 (38-37/64) -
Depth
mm(inch)
840 (33-5/64) 370 (14-9/16) -
Product dimension (Panel)
H×W×D mm, inch
33.5×950×950
(1-11/32×37-13/32×37-13/32)
- -
Packing dimension
Height
mm(inch)
302 (11-57/64) 1642 (64-41/64) -
Width
mm(inch)
898 (35-3/8) 1095 (43-7/64) -
Depth
mm(inch)
898 (35-3/8) 529 (20-53/64) -
Weight
(NET) k
g
(lb) 20 (44) 128 (282) -
(GROSS)
k
g
(lb) 27 (60) 140 (309) -
Panel (NET)
k
g
(lb) 5 (11) - -
Layers limit (actually) 11 (12) 1 (2) -
Operation condition
Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
Heat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
Max Working Pressure HP/LP Mpa (bar) 4.15/2.70 (41.5/27.0) -
P
I
P
I
N
G
Pipe diameter mm (inch) (Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8) (Liquid)Ø12.7(1/2) (Gas)Ø25.4(1) -
Connecting method ared type (Liquid)ared type (Gas)brazing connection -
Standard length m(ft) 7.5 (24.6) -
Pipe length range m (ft) 5 ~ 60 m (16.4 ~ 196.9) -
Indoor unit & Outdoor unit height difference m (ft)
30 m(OD located lower) / 30 m(OD located higher) (98.4 / 98.4) -
Add gas amount
g
/m (oz/ft) 80
g
/m (0.860) -
Pipe length for additional gas m (ft) 30m (98.4) -
*1 In case it is necessary to indicate the air ow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certied models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classication is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 η
s,c
and η
s,h
classication is at 230V(400V) only in accordance with EN-14825. For heating, η
s,h
indicates the value of only Average heating season.
*7 H:High at setting 5 stage (Level 5), M:Middle at setting 5 stage (Level 3), L:Low at setting 5 stage (Level 1)
SM830276-00_欧州向け R32シングル TD&SM.indb 8 2019/02/27 11:54:11