1-12-1-1-16
1
Refrigerant charging
Addition amount of refrigerant [
g
/m]
Tube diameter
Main tube Branch tube
L La, Lb La, Lb, Lc Lc, Ld, Le, Lf
U-200PZH2E8
TWIN
Liquid tube : ø 9.52
Gas tube : ø 25.4
60 45 - -
TRIPLE 60 - 45 -
DOUBLE TWIN 60 45 - 20
U-250PZH2E8
TWIN
Liquid tube : ø 12.7
Gas tube : ø 25.4
80 45 - -
DOUBLE TWIN 80 45 - 45
Make additional charges by adding up tube length in an order of main tube (L) branch tube (La Lb Lc wide diameter) and then selecting the amount of
refrigerant corresponding to the remaining (after 30m for the twin connection and after 20m for the triple/double-twin connections) liquid tube diameter and
tube length from the table above.
Wiring
Power supply
(220-230-240V~)
Indoor unit
Indoor unit
Indoor unit
Indoor unit Outdoor unit
Control
cable
Control
cable
Control
cable
Control
cable
protective
earth
protective
earth
(TRIPLE type)
protective
earth
protective
earth
Circuit breaker
Switch
protective earth
: functional earthing
(for the shielded cable)
(DOUBLE TWIN type)
Power supply
(220-230-240V~)
Power supply
(220-230-240V~)
Power supply
(220-230-240V~)
Power supply
(380-400-415V 3N~)
SM830276-00_欧州向け R32シングル TD&SM.indb 16 2019/02/27 11:54:30