EasyManua.ls Logo

Panasonic F3 - Outdoor Unit Specifications: Oceania; Single Split Models

Panasonic F3
17 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
Oceania
Model Name
U-60PZ2R5 U-71PZ2R5 U-100PZ2R5 U-125PZ2R5 U-140PZ2R5
Power source 230 - 240 V
50 Hz
Cooling capacity
kW
6.0 7.1 10.0 12.5 14.0
BTU/h
20,500 24,200 34,100 42,700 47,800
Heating capacity
kW
6.0 7.1 10.0 12.5 14.0
BTU/h
20,500 24,200 34,100 42,700 47,800
Sound pressure level
(Cooling / Heating)
dB(A)
46 / 48 49 / 49 52 / 52 55 / 55 56 / 56
Sound power level
(Cooling / Heating)
dB(A)
65 / 66 67 / 67 68 / 67 70 / 70 71 / 71
Unit dimensions
(H×W×D)
mm
695×875×320 695×875×320 996×980×370 996×980×370 996×980×370
Net weight
kg
44 44 90 94 94
Operation condition temperature range
• Cooling mode : -10°C~43°C DB • Heating mode : -15°C~24°C DB
Oceania
Model Name
U-100PZ2R8 U-125PZ2R8 U-140PZ2R8
Power source 400 - 415 V 3N
50 Hz
Cooling capacity
kW
10.0 12.5 14.0
BTU/h
34,100 42,700 47,800
Heating capacity
kW
10.0 12.5 14.0
BTU/h
34,100 42,700 47,800
Sound pressure level
(Cooling / Heating)
dB(A)
52 / 52 55 / 55 56 / 56
Sound power level
(Cooling / Heating)
dB(A)
68 / 67 70 / 70 71 / 71
Unit dimensions
(H×W×D)
mm
996×980×370 996×980×370 996×980×370
Net weight
kg
90 94 94
Operation condition temperature range
• Cooling mode : -10°C~43°C DB • Heating mode : -15°C~24°C DB
Rated conditions
Cooling : Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.
Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.
Outdoor unit
Single Split Outdoor Unit (R32)
Specications
01_320325_Eng.indb 16 2020/01/24 14:35:52

Related product manuals